Caution
When the flue pipes are dis-assembled, new seals must be used
for the reassembly!
6.4.7
Outlets
Important
When codes of practice dictate the use of a terminal guard use a
suitable guard of stainless steel construction. There must be a
clearance of at least 50 mm between any part of the terminal and
the guard.
Fig.16
Outlets
AD-3000707-01
N
I
I
G
F
M
I
A
A
F
H
J,K
D
E
H
Likely flue positions requiring a flue terminal guard
C
R
A
I
J,K
I
L
S
B
T
U
Tab.12 Terminal position with minimum distance
Directly below an opening, air brick, opening windows, etc.
300 mm
Above an opening, air brick, opening window etc.
300 mm
Horizontally to an opening, air brick, opening window etc.
300 mm
Below gutters, soil pipes or drain pipes.
25 (75) mm
Below eaves.
25 (200) mm
F
Below balconies or car port roof.
25 (200) mm
G
From a vertical drain pipe or soil pipe.
25 (150) mm
From an internal or external corner.
25 (300) mm
I
Above ground, roof or balcony level.
300 mm
J
From a surface or boundary line facing a terminal.
600 mm
K
From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
1200 mm
600 mm
L
From an opening in carport (e.g. door, window) into the dwelling.
1200 mm
M
Vertically from a terminal on the same wall.
1500 mm
N
Horizontally from a terminal on the same wall.
300 mm
R
From adjacent wall to flue (vertical only).
300 mm
S
From an adjacent opening window (vertical only).
1000 mm
6 Installation
7703046 - 01 - 23072018
Paramount five 30 – 115
45