Tab.22 Storage tank setpoints
Lev
el
Domestic water stor
age tank
Buffer storage tank
A
Nominal value
(prog. no. 1610)
Buffer setpoint
(drag-pointer)
Setpoint solar heat
ing
(prog. no. 2055)
B
Charging temp max
(prog. no. 5050)
Charging temp max
(prog. no. 4750)
C
Storage tank temp
max
(prog. no. 5051)
Storage tank temp
max
(prog. no. 4751)
Swimming pool temp
max
(prog. no. 2070)
(1) Program no. 2065 can be used to set whether the swimming pool is charg
ed first, between the domestic water and the buffer storage tank or last.
For more information, see
Charging priority solar (2065), page 98
Charging time relative prio (3825)
If the preferred storage tank cannot be charged in accordance with the
charging control (e.g. if the temperature difference between the priority
storage tank and the collector is too small), priority will be given to the next
storage tank or the swimming pool during the time set here.
Waiting time relative prio (3826)
Transfer of priority is delayed by the time selected here.
Waiting time parallel op (3827)
Parallel operation is feasible when using solar primary pumps subject to
there being sufficient solar energy available. For this, in addition to the
storage tank currently being heated, the next storage tank in the priority
order can also be heated in parallel. The storage tank switching on for
parallel operation can be delayed and stepped by the value set here.
The setting "- - -" switches off parallel operation.
Delay secondary pump (3828)
The start-up of the secondary pump can be delayed to ensure that it only
switches on if the primary circuit is already at the correct temperature.
Collector start function (3830)
If the temperature at the collector with the pump turned off is not
measured correctly (e.g. with vacuum tubes), then a periodic switching on
of the pump is possible.
Caution
The temperatures at certain collectors cannot be measured
correctly if the pump is switched off. For this reason, the pump
must be activated from time to time.
Min run time collector pump (3831)
The collector pump is periodically switched on for the running time set
here.
Collector start function on (3832) and Collector start function
off (3833)
The time when the collector start function starts or stops is set here.
Collector start funct grad (3834)
As soon as there is a temperature increase on the collector sensor, the
collector pump switches on. The higher the value selected here, the
greater the temperature rise must be.
9 Settings
106