6 Installation
6.1
General
Warning
Risk of injury!
Objects (e.g. tools) that are carelessly placed on the unit lead to a
risk of injuries and damage.
Do not place any objects on the unit. Even for a short time!
6.2
Hydraulic connections
6.2.1
Connecting the heating circuit
Connect the heating circuit with flat seal screw connections to boiler flow
and boiler return.
Disconnector valves have to be installed into the flow and return. To
facilitate the assembly, the shut-off set ADH (accessory) may be used.
Disconnector valves have to be installed into the flow and return. To
facilitate the assembly, the shut-off set ADH or AEH (accessory) may be
used.
Important
Installing filter.
Installation of a filter is recommended in the heating return. In the
case of old plants, the whole heating plant should be thoroughly
flushed before installation.
6.2.2
Safety valve
Mount the membrane expansion vessel with the heating systems closed.
Caution
The connecting pipe between boiler and safety valve must not be
blockable.
The installation of pumps and fittings or pipe reducer pieces is not
permissible. The blow-off line of the safety valve must be
designed in such a way that the pressure does not increase when
the safety valve responds. It must not be routed to the outside, the
opening must be clear and observable. Any heating water that
may possibly escape should be safely drained off.
Caution
The blow-off line of the safety valve must be designed in such a
way that the pressure does not increase when the safety valve
responds. It must not be routed to the outside, the opening must
be clear and observable. Any heating water that may possibly
escape should be safely drained off.
6.2.3
Connecting the expansion vessel
1. Ensure that an expansion vessel with a sufficient fill quantity and
correct inlet pressure is present.
2. Install the expansion vessel on the disconnector valve (ADH/AEH
accessory) for the flow pipe from the Paramount boiler.
Fig.12
Installation of disconnector valves
RA-0000056
6 Installation
38
Paramount five 30 – 115
7703046 - 01 - 23072018