Burner control
Prog. no.
Level Standard value
Prepurge time
9500
E
15 s
Required output prepurging
9504
E
Paramount 30: 14,5
kW; Paramount 40:
19.5 kW
Paramount 50: kW;
Paramount 60: 35,0
kW; Paramount 80:
50,0 kW; Paramount
95: 50,8 kW; Para‐
mount 115: 56.6 kW
Required output ignition
1)
9512
E
Paramount 30: 14,5
kW; Paramount 40:
19.5 kW
Paramount 50: kW;
Paramount 60: 35,0
kW; Paramount 80:
50,0 kW; Paramount
95: 50,8 kW; Para‐
mount 115: 56.6 kW
Required output LF
1)
9524
E
Paramount 30: 5,6
kW; Paramount 40:
9.0 kW
Paramount 50: 10,0
kW; Paramount 60:
14,0 kW; Paramount
80: 21,0 kW; Para‐
mount 95: 20,0 kW;
Paramount 115: 25.0
kW
Required output HF
1)
9529
E
Paramount 30: 30,0
kW; Paramount 40:
38.0 kW
Paramount 50: 50,0
kW; Paramount 60:
58,0 kW; Paramount
80: 77,0 kW; Para‐
mount 95: 95,0 kW;
Paramount 115:
115,0 kW
Postpurge time
9540
E
10 s
Fan output/speed slope
9626
E
Paramount 30: 214,3;
Paramount 40: 150.0
Paramount 50: 111,3;
Paramount 60: 98,9;
Paramount 80: 69,6;
Paramount 95: 63,1;
Paramount 115: 57,0
Fan output/speed Y-section
9627
E
Paramount 30: 100,0;
Paramount 40: 100.0
Paramount 50: 138,0;
Paramount 60: 70,0;
Paramount 80: 240,0;
Paramount 95: 320,0;
Paramount 115:
300,0
(1) the kW settings are approximate values. Exact values can be determined by the gas meter for example.
Prog. no.
Level Standard value
Error/alarm message
Maintenance
Setpoint manual control
9 Settings
7703046 - 01 - 23072018
Paramount five 30 – 115
83