3 Technical specifications
3.1
Homologations
3.1.1
Regulations and standards
Beside the general technical rules, the relevant standards, regulations,
ordinances and guidelines should be followed:
DIN 4109: Sound insulation in buildings
DIN EN 12828: Heating systems in buildings –, planning domestic hot
water heating systems
Federal Immission Control Ordinance 1. BImSchV
DVGW-TRGI 1986 (DVGW-worksheet G 600): Technical Rules for gas
installation
TRF: Technical Rules LPG
DVGW-Data sheet G - 613 Gas appliances- Installation, maintenance
and operating instructions
DIN 18380: Installation of central heating systems and hot water supply
systems (VOB)
DIN EN 12831: Heating systems in buildings -, Method for calculation of
the design heat load
DIN 4753: Domestic hot water calorifiers. Domestic hot water heating
system and storage tanks for heated water
DIN 1988: Technical rules for drinking water installations (TRW)
DIN EN 60335-2-102: Safety of electrical appliances for household use
and similar purposes: Special requirements for gas-, oil- und solid fuel
appliances with electrical connections
Fuel Ordinance, State Ordinances
Regulations of the local Electricity Board
Obligation to register (possibly. Group Exemption Regulation )
ATV-Code-of-practice M251 of the waste water technology association
Regulations of the public authorities for the run-off of condensate.
3.2
Technical data
3.2.1
Technical data – Boiler space heaters
Tab.2
Technical parameters for boiler space heaters
Model
Paramount 30
Paramount 40
Condensing boiler
Yes
Yes
No
No
B1 boiler
No
No
Cogeneration space heater
No
No
Combination heater
No
No
Rated heat output
Prated
kW
29
37
Useful heat output at rated heat output and high tem
perature mode
P
4
kW
29.2
37.0
Useful heat output at 30% of rated heat output and low
P
1
kW
9.8
12.4
Seasonal space heating energy efficiency
ƞ
s
%
93
93
Useful efficiency at rated heat output and high temper
ƞ
4
%
87.6
87.7
Useful heat output at 30 % of rated heat output and low
ƞ
1
%
97.9
97,8
Auxiliary electricity consumption
At full load
elmax
kW
0.055
0.070
At part load
elmin
kW
0.021
0.025
In standby mode
P
SB
kW
0.003
0.003
3 Technical specifications
7703046 - 01 - 23072018
Paramount five 30 – 115