Burner running time min (2241)
Here, the period following the commissioning of the burner is selected
during which the shutdown differential is increased by 50%. However, this
setting cannot guarantee that the burner remains operational for the
selected period.
Burner off time min (2243)
The boiler minimum pause time only takes effect between heating
requirements coming following in sequence. The boiler minimum pause
time blocks the boiler for a set time.
SD burner off time (2245)
When a switching difference is exceeded,Burner off time min (prog. no.
2243) is aborted. The boiler starts despite pausing time.
Pump overrun time (2250) and Pump overr time after DHW
(2253)
The delay times of the pumps are controlled according to heating mode or
drinking water mode.
Frost prot plant boiler pump (2300)
Depending on the current outside temperature, the boiler pump switches
on even though no heat request exists (see table below).
Important
The solid fuel tank frost protection only functions if the frost
protection system (parameter 6120) is switched on.
Outside temperature
Pump
...-4 °C
ON continuously
-5 °C - +1.5 °C
ON approximately every 6 hours for
10 minutes
+1.5 °C...
OFF continuously
Off
The function is switched off.
On
The function is switched on.
Boiler pump on heat gen lock (2301)
Stop of boiler pump in case of activated manual heat generation lock (e.g.
via H1).
Off: Switching off not activated
On: Switching off activated
Impact heat generation lock (2305)
This parameter is used to set whether the heat generator lock should be
effective only for heating requests or also for DHW requests.
Heating mode only: Only heating requests are locked. DHW requests
are still operated.
Heating and DHW mode: All heating and DHW requests are locked.
Temp differential max (2316)
When the pump reaches the maximum speed with the setting temperature
rise nominal, the temperature difference increases via the boiler. The
value set in temperature rise maximum is not exceeded. This is achieved
by reducing the boiler setpoint to the current return temperature plus the
value shown here.