IOL MA8 PN DI8
72
PHOENIX CONTACT
4022_en_A
6.2
Status LEDs
The IOL MA8 PN DI8 features LEDs to indicate the status of the device, IO-Link
communication, and I/O.
Figure 6-1
IOL MA8 PN DI8 LEDs
P3
P4
P7
P8
P1
DI C/Q
DI C/Q
DI C/Q
DI C/Q
P2
P5
P6
NET
AC
T
LI
N
K
AC
T
LI
N
K
X2
X1
MOD
Upon power up, the NET and MOD LED stay solid red until the IOL MA8 PN DI8 is fully
functional.
Table 6-1
LED indication
LED name
Status
Indication
MOD (Module
Status)
Off
No errors or there is no PLC connection
Flashing green/red
Self-test
Flashing green
Standby or not configured
Solid green
Normal operation
Flashing red
One or more errors detected when NET is off
Fatal error when NET LED is also flashing red
Solid red
Maintenance required
NET (Network
Status)
Off
No PLC connection
Flashing green/red
Self test
Flashing green
An IP address is configured, but no connections
are established
Solid green
PLC connection established
Flashing red
Fatal error when MOD LED is also flashing red
Solid red
Duplicate IP address on network