IOL MA8 PN DI8
30
PHOENIX CONTACT
4022_en_A
3.
Review the “Port Status” and “IO-Link State” fields.
If a digital input or output device is connected to an IOL MA8 PN DI8 port, there is no valid
data until the port is set to the correct Port Mode.
Review the “Device IO-Link Version” field.
–
If the field is blank, it is not a valid IO-Link device, which could mean that it is a digital
device and the port is not configured for digital input or digital output.
–
The field displays the Device IO-Link version.
Optionally, review the “Configured Minimum Cycle Time” field value. The “Configured
Minimum Cycle Time” field is the minimum cycle time allowed for the port. The “Actual Cycle
Time” field value is negotiated between the IOL MA8 PN DI8 and the IO-Link device, and
will be at least as long as the greater of the “Configured Minimum Cycle Time” and the
“Device Minimum Cycle Time” fields.
Verify that the “Auxiliary Input Bit Status” field displays
On
, if the device is connected to the
DI pos. circuit.
Table 5-4
Port status and IO-Link state description
Field name
Status
Indication
Port Status
Operational, PDI
Valid
An IO-Link device is operating on the port that has received valid PDI data.
Operational
An IO-Link device is operating on the port that has not received valid PDI data.
Inactive
One of the following conditions exists:
–
A valid IO-Link device is not connected to the port.
–
A digital input or output device is connected to the port but the configured Port
Mode is not correct.
IO-Link State
Operate
Port is functioning correctly in IO-Link mode but has not received valid PDI data.
This may also display during a data storage upload or download.
Init
The port is attempting initialization.
Reset
One of the following conditions exists:
–
The Port Mode configuration is set to Reset.
–
The Port Mode configuration is set to DigitalIn or DigitalOut.
DS: Wrong Sensor
Hardware failure (IO-Link LED also flashes red) because there is Data Storage on
this port, which does not reflect the attached device.
DV: Wrong Sensor
Hardware failure (IO-Link LED also flashes red) because Device Validation is
configured for this port and the wrong device is attached.
DS: Wrong Size
Hardware failure (IO-Link LED also flashes red) because the size of the
configuration on the device does not match the size of the configuration stored on
the port.
Comm Lost
Temporary state after a device is disconnected and before the port is re-initialized.
Pre-operate
Temporary status displayed when the device:
–
Is starting up after connection or power-up.
–
Uploading or downloading automatic data storage.