Web manager interface
4022_en_A
PHOENIX CONTACT
21
Configured Minimum Cycle
Time
This is the minimum cycle time at which the IO-Link will allow the port to operate. The
Actual Cycle Time, which is negotiated between the IO-Link device and the IOL MA8 PN
DI8, will be at least as long as the greater of the Configured Minimum Cycle Time and the
Device Minimum Cycle Time (see
“Editing the IOL MA8 PN DI8 port settings” on
Data Storage Capable
Displays whether the IO-Link device on a port supports the data storage feature. The IO-
Link device manufacturer determines if the device supports data storage.
Automatic Data Storage
Configuration
Displays whether a port is configured to automatically upload data from the IO-Link device
or download data from the IOL MA8 PN DI8 to the IO-Link device.
Disabled
indicates
automatic upload or download are not enabled.
Auxiliary Input (AI) Bit Status
Displays the status of the auxiliary digital input DI signal.
Device PDI Data Length
The supported Device PDI Data Length, in bytes, as stored in ISDU Index 0.
PDI Data Valid
Current status of PDI data as received from the IO-Link device.
Last Rx PDI Data (MS Byte
First)
The last Rx PDI data as received from the IO-Link device.
Device PDO Data Length
The supported Device PDO Data Length, in bytes, as stored in ISDU Index 0.
PDO Data Valid
Status of PDO data being received from the controller(s).
Last Tx PDO Data (MS Byte
First)
The last Tx PDO data.
Time Since Initialization
The time since the last port initialization.
Process Data Errors
The number of process data errors the port received.
Process Data Retries
The number of process data retries the port performed.
Total Events
The total number of events received on this port.
First Events
Up to the first, or oldest, three events received on this port.
Last Events
Up to the last, or most recent, three events received on this port.
ISDU Statistics
ISDU Read Cmd Attempts
The number of read ISDU command attempts.
ISDU Read Cmd Errors
The number of read ISDU command errors.
ISDU Write Cmd Attempts
The number of write ISDU command attempts.
ISDU Write Cmd Errors
The number of write ISDU command errors.
Table 5-1
“IO-Link Diagnostics” page field descriptions [...]
Field name
Description
Summary of Contents for IOL MA8 PN DI8