Device validation
Device validation is supported by many IO-Link devices. Device Validation Mode provides
these options:
–
None:
Disables Device Validation Mode.
–
Compatible:
Permits a compatible IO-Link device (same Vendor ID and Device ID) to
function on the corresponding port.
–
Identical:
Permits only the same IO-Link device (same Vendor ID, Device ID, and serial
number) to function on the corresponding port.
To configure device validation:
1.
Click the “Configuration” tab, and then click the “IO-Link” subtab.
2.
Click the “EDIT” button.
3.
From the “Device Validation Mode” drop-down menu, select
Compatible
or
Identical
.
4.
Click the “GET ATTACHED” button or manually enter the Vendor ID, Device, ID, and
serial number.
5.
Click the “SAVE” button.
If the wrong or incompatible device is connected to the port, the IOL MA8 PN DI8 port
LED flashes red and no IO-Link activity occurs on the port until the issue is resolved.
In addition, the “IO-Link Diagnostics” page displays the following information.
Figure 5-9
“IO-Link Diagnostics” page indicating incorrect sensor connection
A device serial number is required to select
Identical
. Without the serial number, the IOL
MA8 PN DI8 cannot identify a specific device.