background image

IOL MA8 PN DI8

18

PHOENIX CONTACT

4022_en_A

1.

If necessary, log in to the IOL MA8 PN DI8.

2.

Click the “Diagnostics” tab, and then click the desired subtab. For example, to show the 

“IO-Link Diagnostics” page, click the “IO-Link” subtab. 

Figure 5-1

“IO-Link Diagnostics” page

3.

Use the scroll bars to view all available information.

4.

This data is updated with the “LIVE update” function providing constant updates. If 

desired, click the “STOP LIVE UPDATES” button to stop the function. To update data 

immediately, click the “UPDATE” button. Click the “RESET STATISTICS” button to 

reset the statistics fields.

Summary of Contents for IOL MA8 PN DI8

Page 1: ...User manual UM EN IOL MA8 PN DI8 IO Link to PROFINET and Modbus TCP gateway...

Page 2: ...KG Flachsmarktstra e 8 32825 Blomberg Germany phoenixcontact com 4022_en_A IO Link to PROFINET and Modbus TCP gateway Designation Order No IOL MA8 PN DI8 1072838 User manual This user manual is valid...

Page 3: ...cture 5 2 3 System example 6 3 Installation 7 3 1 Mounting 7 3 2 Data interfaces 8 3 2 1 Connecting the Ethernet cable 8 3 3 Connecting the power supply 9 3 4 Connecting devices to IOL MA8 PN DI8 port...

Page 4: ...ies 48 5 2 8 Configuration files 51 5 3 Device maintenance 53 5 3 1 Firmware 53 5 3 2 Accounts 55 5 3 3 Log files 57 5 3 4 Device snapshot 59 5 4 Attached devices 60 5 4 1 IODD files 60 5 4 2 IO Link...

Page 5: ...be familiar with the relevant safety concepts of automation technology as well as applicable standards and other regulations Qualified application programmers and software engineers The users must be...

Page 6: ...he device yourself Opening the device or making changes to it is not permitted Do not repair the device yourself but replace it with an equivalent device Repairs may be carried out only by the manufac...

Page 7: ...atures two Ethernet ports status LEDs and connectors for power and IO Link ports Figure 2 1 IOL MA8 PN DI8 structure Table 2 1 IOL MA8 PN DI8 structure Item Description 1 Power connector 2 Port 1 IO L...

Page 8: ...orts RJ45 11 Digital input and IO Link port status LEDs 12 NET status LED 13 MOD status LED 14 Reset button Table 2 1 IOL MA8 PN DI8 structure Item Description SIO PSR switch PSR CT F SEN 1 8 Ord No 2...

Page 9: ...he housing cover and carefully push the device toward the mounting surface 2 3 After the foot is snapped on to the DIN rail verify that it is attached securely Figure 3 1 DIN rail mounting To remove 1...

Page 10: ...e chain so it is recommended to overload and test for performance in the environment The application may also limit the total number of ports that may be installed Some basic guidelines are listed bel...

Page 11: ...rect connection may result in damage to equipment and or serious personal injury Only qualified personnel may connect the power start up and operate this device According to the safety instructions in...

Page 12: ...y configure IO Link parameters for each port Connecting digital input devices to IOL MA8 PN DI8 ports Use the following procedure to connect a digital input device to an IO Link port 1 Insert the IO L...

Page 13: ...and operate a digital input or output device 1 Insert the IO Link device negative wire into the L position until the wire is fully secure 2 Insert the IO Link device positive wire into the L position...

Page 14: ...IOL MA8 PN DI8 12 PHOENIX CONTACT 4022_en_A...

Page 15: ...web based graphical user interface GUI allows management of the IOL MA8 PN DI8 from anywhere in the network using a standard browser Comprehensive configuration and diagnostic functions including a w...

Page 16: ...ddress see LAN settings on page 47 Load the appropriate IODD files see IODD files on page 60 Configure the IO Link ports see IO Link configuration on page 31 If the web server does not load first chec...

Page 17: ...up 4022_en_A PHOENIX CONTACT 15 4 2 2 Home page The Home page displays general system information Figure 4 3 Home page 4 2 3 Selecting a language Click the Flag icon to select the interface language e...

Page 18: ...IOL MA8 PN DI8 16 PHOENIX CONTACT 4022_en_A...

Page 19: ...Web manager interface 4022_en_A PHOENIX CONTACT 17 5 Web manager interface 5 1 Diagnostics This chapter provides information about the diagnostics pages To access the diagnostics pages...

Page 20: ...tics page click the IO Link subtab Figure 5 1 IO Link Diagnostics page 3 Use the scroll bars to view all available information 4 This data is updated with the LIVE update function providing constant u...

Page 21: ...Web manager interface 4022_en_A PHOENIX CONTACT 19 5 1 1 IO Link diagnostics Use the IO Link Diagnostics page to determine the status of the IO Link configuration Figure 5 2 IO Link Diagnostics page...

Page 22: ...ists The Port Mode configuration is set to Reset The Port Mode configuration is set to DigitalIn or DigitalOut DS Wrong Sensor Hardware failure IO Link LED also flashes red because there is Data Stora...

Page 23: ...Length in bytes as stored in ISDU Index 0 PDI Data Valid Current status of PDI data as received from the IO Link device Last Rx PDI Data MS Byte First The last Rx PDI data as received from the IO Lin...

Page 24: ...CT 4022_en_A 5 1 2 PROFINET IO diagnostics The PROFINET IO Diagnostics page may be useful when trying to troubleshoot PROFINET communications and port issues related to PROFINET configuration Figure 5...

Page 25: ...aster can process them PROFINET IO Frames Transmitted The total number of transmitted PROFINET IO frames PROFINET IO Transmit Errors The number of errors when transmitting PROFINET IO frames PROFINET...

Page 26: ...est Msg Response Time Displays the maximum time period required to process all commands within an ISDU request message The response is not available until all ISDU command s contained in the request h...

Page 27: ...IX CONTACT 25 5 1 3 Modbus TCP diagnostics The Modbus TCP Diagnostics page may be useful when trying to troubleshoot Modbus TCP communications or port issues related to the Modbus TCP configuration Fi...

Page 28: ...message that specifies a non Modbus protocol Unsupported Function Code Errors Displays the number of invalid Modbus function code errors These errors occur when the IOL MA8 PN DI8 receives a message...

Page 29: ...SDU Responses Displays the number of unexpected ISDU responses Unexpected responses may occur when an ISDU response is received after the ISDU request has timed out This typically requires setting the...

Page 30: ...tions Displays the number of OPC UA clients actively connected 5 2 Configuration Depending on environment the IOL MA8 PN DI8 may not need to change many of the default options 5 2 1 Preparing for port...

Page 31: ...interface 4022_en_A PHOENIX CONTACT 29 1 If necessary log in to the IOL MA8 PN DI8 2 Click the Diagnostics tab and then the IO LINK subtab to open the IO Link Diagnostics page Figure 5 6 IO Link Diagn...

Page 32: ...rational An IO Link device is operating on the port that has not received valid PDI data Inactive One of the following conditions exists A valid IO Link device is not connected to the port A digital i...

Page 33: ...le Time value This page provides special features such as Data Storage Device Validation and Data Validation Editing the IOL MA8 PN DI8 port settings If an IO Link device is attached to the port no co...

Page 34: ...ettings page 4 Make appropriate selections for the device connected to that port see Table 5 5 Click the EDIT button for all ports to quickly configure all port parameters NOTE Do not enable Automatic...

Page 35: ...ate The valid range is 4 538 ms If the Minimum Cycle Time field is set to the default value the IOL MA8 PN DI8 negotiates with the IO Link device for its minimum cycle time The IO Link Diagnostics pag...

Page 36: ...Default Off The data storage parameters on the IOL MA8 PN DI8 are downloaded to the connected IO Link device if The Automatic Download option is enabled The data stored on the IOL MA8 PN DI8 port con...

Page 37: ...idation Mode is selected The Serial Number can be manually entered in this field or click the GET ATTACHED button and the IO Link automatically populates the field Data Validation Mode Default None Th...

Page 38: ...IOL MA8 PN DI8 saves the data storage parameters if the data storage is empty from the IO Link device to the IOL MA8 PN DI8 When this option is enabled and another IO Link device is connected differen...

Page 39: ...n the IOL MA8 PN DI8 4 Click the UPLOAD button 5 Click the CONTINUE button to the Continue to upload the data storage on IO Link port number message 6 Click the OK button to the Data storage upload su...

Page 40: ...then click the IO Link subtab 2 Click the EDIT button 3 From the Device Validation Mode drop down menu select Compatible or Identical 4 Click the GET ATTACHED button or manually enter the Vendor ID De...

Page 41: ...appropriate fields 5 Click the SAVE button If data validation fails the IO Link port LED flashes red and the IO Link Diagnostics page displays an error 5 2 3 PROFINET IO configuration Use the PROFINE...

Page 42: ...bus TCP Settings page to configure Modbus TCP with the IOL MA8 PN DI8 Editing Modbus TCP settings 1 If necessary open the IOL MA8 PN DI8 interface with the browser using the IP address Click the Confi...

Page 43: ...Scroll down to see all editable parameters 4 Scroll to the top of the page and click the SAVE button Make sure that the port now displays the EDIT button If it displays the SAVE and CANCEL buttons th...

Page 44: ...Data passed through as received Word 16 bit byte swap Data is byte swapped in word format Dword 32 bit byte swap Data is byte swapped in dword format Reverse registers Data passed through after being...

Page 45: ...PDO data Clear Event Code After Hold Time Default True If enabled the IOL MA8 PN DI8 clears any event code reported in the PDI data block after the Event Active Hold Time Values are True enable check...

Page 46: ...e Units Valid units ms milliseconds sec seconds min minutes hours days Transfer Mode Settings Slave Mode Device ID Default 1 The Modbus Device ID used to access this IO Link port Range 1 247 PDI Recei...

Page 47: ...port or ports to configure Figure 5 14 Editing a port on the OPC UA Settings page 3 Make appropriate selections for the device connected to that port 4 Click each EDIT button and open all ports to qu...

Page 48: ...ork around for faulty OPC UA clients that require unique browsenames Default Disable Enables an alternative set of browse names where each node s browse name is unique Normally only browse paths are r...

Page 49: ...settings may be reviewed or changed To view and edit LAN settings 1 Click the Configuration tab and then click the LAN subtab Figure 5 15 LAN Settings page 2 Scroll to see all the fields and values 3...

Page 50: ...Link slaves from the Attached Devices Port page in the user interface LED Flash Forces the IO Link port LEDs on the IOL MA8 PN DI8 to flash which allows easy identification of a particular unit Click...

Page 51: ...es of event that can be generated Table 5 8 IO Link Test Event Generator Descriptions Field name Function Port The port number to send an event Mode This is the first item in the event generated Singl...

Page 52: ...eck event 0x0001 Generates a s_pdu_flow event 0x0002 Generates a m_pdu_check event 0x0003 Generates a s_pdu_illegal event 0x0004 Generates a m_pdu_illegal event 0x0005 Generates a s_pdu_buffer event 0...

Page 53: ...he configuration files for the IOL MA8 PN DI8 includes all port settings network settings and encrypted passwords 1 Click the Configuration tab and then click the CONFIG FILES subtab Figure 5 19 Load...

Page 54: ...ad options on the Load or Save Configuration page 2 Click the Choose File button and navigate to the configuration file dcz extension 3 Click the LOAD button 4 Click the OK button to close the Configu...

Page 55: ...es Hostname network settings DHCP Static static IP address static network mask and static IP gateway Removes any stored data in the listed fields 5 3 Device maintenance 5 3 1 Firmware The IOL MA8 PN D...

Page 56: ...all button 7 Click the CONTINUE button in the Update Image message 8 When finished click the OK button to close the Update Image Successful message 9 After an image is updated always click the REBOOT...

Page 57: ...read and write access See Table 5 9 to see how permissions are granted NOTE After an application subassembly is updated always reboot the device Table 5 9 User privilege descriptions Page Admin Operat...

Page 58: ...figured 4 Click the checkbox for the desired password level ADMIN OPERATOR or USER 5 Enter the new password in the appropriate New Password and Confirm Password fields 6 Click the Apply button The nex...

Page 59: ...100 kB 5 3 3 1 View a log file To view a log file 1 Click the Device Maintenance tab and then click the LOG FILES subtab 2 Select the desired file from the select log file drop down menu Figure 5 26 s...

Page 60: ...downloads files 5 3 3 3 Clear a log file Use this procedure to clear a log file 1 Click the Device Maintenance tab and then click the LOG FILES subtab 2 Select the desired file from the select log fi...

Page 61: ...Additionally a comprehensive support file may be downloaded to assist when troubleshooting 1 Click the Device Maintenance tab and then click the DEVICE SNAPSHOT subtab Figure 5 27 Device Snapshot page...

Page 62: ...dardDefinitions1 1 xml IODD StandardUnitDefinitions1 1 xml Preparing IODD files to upload Some IODD zip files contain the xml files and supporting image files for a single product This type of zip fil...

Page 63: ...to the file location 4 Highlight the zip file click the Open button and then click the UPLOAD button 5 If necessary click the OK button If desired click the file name in the IODD FILENAME column to v...

Page 64: ...ete 3 Click the DELETE SELECTED button 4 Click the CONTINUE button to confirm deletion 5 4 2 IO Link device configuration summary The IO Link Device Configuration Summary page provides basic device co...

Page 65: ...2_en_A PHOENIX CONTACT 63 1 Click the Attached Devices tab and then the SUMMARY subtab Figure 5 31 IO Link Device Configuration Summary page The summary page takes several minutes to completely load a...

Page 66: ...ink Device Port n page where n is the selected port Figure 5 32 Details for a selected port on the IO Link Device Port n page 5 4 3 Port parameters This chapter discusses using the IO Link Device Port...

Page 67: ...vice Port n graphical interface IO Link Device ISDU Interface Port n Indexed Service Data Unit Can be used with or without IODD files loaded see Editing parameters IO Link device ISDU Interface Port n...

Page 68: ...5 34 IO Link Device page showing index and subindex information 3 To access the process data click the Process Data option from the drop down menu next to the port number Figure 5 35 Process data on...

Page 69: ...parameters using the Edit button on the IO Link Device Port n graphical interface page 1 Verify that the Automatic Download Enable for Data Storage option on the IO Link Settings page is not set to On...

Page 70: ...e Figure 5 37 Editable fields on the IO Link Device Port n page 5 Use the sliders to scroll as necessary and then make appropriate parameter changes for the environment 6 Click the SAVE button after e...

Page 71: ...Editing parameters IO Link device ISDU Interface Port n The IO Link Device ISDU Interface Port n group follows these guidelines If necessary convert hexadecimal ISDU index numbers to decimal enter th...

Page 72: ...l form in the ISDU Block Index field 4 If applicable enter the number in decimal form in the ISDU Subindex field 5 Edit the parameter hex and then click the SET button The SET button sends the value t...

Page 73: ...ink configuration on page 31 to reset the port and then set the Port Mode back to IO Link Reboot or power cycle the IOL MA8 PN DI8 Use the Firmware page see Firmware on page 53 to reboot the IOL MA8 P...

Page 74: ...Status Indication MOD Module Status Off No errors or there is no PLC connection Flashing green red Self test Flashing green Standby or not configured Solid green Normal operation Flashing red One or...

Page 75: ...same device Device Validation Mode is enabled and it is not the correct device Data Validation Mode is enabled but there is an error Solid red PDI of the attached IO Link device is invalid Solid gree...

Page 76: ...IOL MA8 PN DI8 74 PHOENIX CONTACT 4022_en_A...

Page 77: ...h IO Link port Read access to ISDU responses from each IO Link port Read access to the port information block for each IO Link port A 1 1 Modbus TCP function codes This table shows the supported Modbu...

Page 78: ...to 125 words Transmit ISDU Request 1301 2301 3301 4301 5301 6301 7301 8301 Write only 4 to 123 words Port information block Continuous block Vendor Name 1501 2501 3501 4501 5501 6501 7501 8501 Read on...

Page 79: ...igure 5 1 IO Link Diagnostics page 18 Figure 5 2 IO Link Diagnostics page 19 Figure 5 3 PROFINET IO Diagnostics page 22 Figure 5 4 Modbus TCP Diagnostics page 25 Figure 5 5 The OPC UA Diagnostics page...

Page 80: ...e Description Files page 61 Figure 5 29 Upload options on the IO Link Device Description Files page 61 Figure 5 30 Missing files notification on the IO Link Device Descriptions Files page 62 Figure 5...

Page 81: ...agnostics page field descriptions 23 Table 5 3 Modbus TCP Diagnostics page field description 26 Table 5 4 Port status and IO Link state description 30 Table 5 5 IO Link Settings page parameters 33 Tab...

Page 82: ...IOL MA8 PN DI8 80 PHOENIX CONTACT 4022_en_A...

Page 83: ...products inspecific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any accompanyi...

Page 84: ...t net products Subsidiaries If there are any problems that cannot be solved using the documentation please contactPhoenix Contact subsidiary Subsidiary contact information is available at phoenixconta...

Reviews: