provides information about the fields on the “IO-Link Diagnostics” page.
Table 5-1
“IO-Link Diagnostics” page field descriptions
Field name
Description
Port Name
This is an optional user-friendly port name, which can be configured in the Configuration
IO-Link page (see
“Editing the IOL MA8 PN DI8 port settings” on page 31
Port Mode
Displays the active device mode:
–
Reset = The port is configured to disable all functionality.
–
IO-Link = The port is configured to IO-Link mode.
–
DigitalIn = The port is configured to operate as a digital input.
–
DigitalOut = The port is configured to operate as a digital output.
Port Status
Displays the port status:
–
Inactive: The port is in an inactive state. Typically, this indicates that the device is
either not attached or not detected.
–
Initializing: The port is in the process of initializing.
–
Operational: The port is operational and, if in IO-Link mode, communication to the IO-
Link device is established.
–
PDI Valid: The PDI data is now valid.
–
Fault: The port has detected a fault and is unable to re-establish communication.
IO-Link State
–
Operate: Port is functioning correctly in IO-Link mode but has not received valid PDI
data. This may also display during a data storage upload or download.
–
Init: The port is attempting initialization.
–
Reset: One of the following conditions exists:
–
The Port Mode configuration is set to
Reset
.
–
The Port Mode configuration is set to
DigitalIn
or
DigitalOut
.
–
DS - Wrong Sensor: Hardware failure (IO-Link LED also flashes red) because there
is Data Storage on this port that does not reflect the attached device.
–
DV - Wrong Sensor: Hardware failure (IO-Link LED also flashes red) because Device
Validation is configured for this port and the wrong device is attached.
–
DS - Wrong Size: Hardware failure (IO-Link LED also flashes red) because the size
of the configuration on the device does not match the size of the configuration stored
on the port.
–
Comm Lost: Temporary state after a device is disconnected and before the port is re-
initialized.
–
Pre-operate: Temporary status displayed when the device:
–
Is starting up after connection or power-up.
–
Uploading or downloading automatic data storage.
Device Vendor Name
Displays the “Device Vendor Name” as stored in ISDU Index 16.
Device Product Name
Displays the “Device Product Name” as stored in ISDU Index 18.
Device Serial Number
Displays the “Device Serial Number” as stored in ISDU Index 21.
Device Hardware Version
Displays the “Device Hardware Version” as stored in ISDU Index 22.
Device Firmware Version
Displays the “Device Firmware Version” as stored in ISDU Index 23.
Device IO-Link Version
The supported device IO-Link version as stored in ISDU Index 0.
Actual Cycle Time
This is the actual, or current, cycle time of the IO-Link connection to the device.
Device Minimum Cycle Time
This is the minimum, or fastest, cycle time supported by the connected IO-Link device.