Technical appendix
4022_en_A
PHOENIX CONTACT
A Technical
appendix
A 1
Modbus TCP interface
The IOL MA8 PN DI8 provides a slave-mode Modbus TCP interface that provides read
access to the Process Data Input (PDI) and Process Data Output (PDO) data blocks for
each IO-Link port.
–
Write access to the PDO data block for each IO-Link port
–
Write access to send ISDU requests to each IO-Link port
–
Read access to ISDU responses from each IO-Link port
–
Read access to the port information block for each IO-Link port
A 1.1
Modbus TCP function codes
This table shows the supported Modbus TCP function codes.
“Modbus TCP configuration” on page 40
for process data block descriptions.
Table A-1
Function codes
Message type
Function codes
Maximum message size
Read holding registers
3
250 bytes (125 words)
Write single register
6
2 bytes (1 word)
Write multiple registers
16 (10 hex)
246 bytes (123 words)
Read/Write holding registers
23 (17 hex)
Write: 242 bytes (121 words)