![Phoenix Contact IOL MA8 PN DI8 User Manual Download Page 39](http://html1.mh-extra.com/html/phoenix-contact/iol-ma8-pn-di8/iol-ma8-pn-di8_user-manual_1551441039.webp)
Web manager interface
4022_en_A
PHOENIX CONTACT
37
Downloading data storage
to the IO-Link device
There are two methods to download Data Storage using the “IO-Link Settings” page:
–
Automatic Download Enable:
An automatic download occurs when the “Automatic
Download Enable” field is set to
On
and one of these conditions exists:
–
The original IO-Link device is disconnected and an IO-Link device whose
configuration data differs from the stored configuration data.
–
The IO-Link device requests an upload and the Automatic Upload Enable option is
set to
Off
.
–
Data Storage Manual Ops:
–
DOWNLOAD: Click the “DOWNLOAD” button to download the data storage from
the selected port to the IO-Link device.
If an IO-Link device with a different Vendor ID and Device ID is attached to the port
and a manual download is attempted, the IOL MA8 PN DI8 issues a hardware fault.
Automatic device
configuration
Use the following steps to use an IOL MA8 PN DI8 port to configure multiple IO-Link devices
with the same configuration parameters.
1.
If necessary, configure the IO-Link device as required for the environment.
2.
Click the “Configuration” tab, and then click the “IO-Link” subtab.
3.
Click the “EDIT” button to select the port where the data is stored on the IOL MA8 PN
DI8.
4.
Click the “UPLOAD” button.
5.
Click the “CONTINUE” button to the Continue to upload the data storage on IO-Link port
[number] message.
6.
Click the “OK” button to the Data storage upload successful on Port [number] message.
7.
Set the Automatic Download Enable option to
On
.
8.
Click the “SAVE” button.
9.
Click the “Diagnostics” tab, and then click the “IO-Link” subtab.
10. Replace the IO-Link device on that port with the IO-Link device for automatic
configuration.
11. Verify that the IO-Link device displays operational Port Status and the appropriate IO-
Link state.
12. Repeat 10 and 11 for each configured device.
Automatic Device
Configuration backup
The following procedure shows how to utilize data storage to automatically back up an IOL
MA8 PN DI8 device configuration.
Use the manual UPLOAD feature to capture the latest settings.
1.
Click the “Configuration” tab, and then click the “IO-Link” subtab.
2.
Click the “EDIT” button for the port to store the data on the IOL MA8 PN DI8.
3.
Select
On
in the drop-down menu for Automatic Data Storage Upload Enable.
4.
Click the “SAVE” button.
When the “Configuration/IO-Link” page is refreshed, the “Storage Contents” field
displays the Vendor ID and Device ID. In addition, the “IO-Link” page displays
Upload-
Only
in the “Automatic Data Storage Configuration” field.
Do not enable both Automatic Upload and Download at the same time, the results are not
reliable among IO-Link device manufacturers.
Summary of Contents for IOL MA8 PN DI8