For your safety
108928_en_02
PHOENIX CONTACT
9 / 84
1.5
UL notes
Additional technical data for UL
CAUTION
– The external circuits intended to be connected to this device shall be galvanically
separated from MAINS supply or hazardous live voltage by reinforced or double
insulation and meet the requirements of SELV/PELV (Class III) circuits of
UL/CSA/IEC 61010-1, -2-201.
– The device has to be built-in the final safety enclosure, which has adequate rigidity
according to UL 61010-1, -2-201 and meets the requirements with respect to spread
of fire.
Information
To install the device according to the UL/CSA/IEC standard, the following rules must be
observed.
– If the equipment is used in a manner not specified, the protection provided by the
equipment may be impaired.
– Minimum temperature rating of the cables to be connected to the field wiring
terminals:
80 °C, AWG 24 ... 16
– Use copper conductors only.
I/O supply U
P
Current consumption
1070 mA, maximum (all inputs set, with supply to the sensors
via clock supplies OUT_T1 and OUT_T2)
Power consumption
32 W, maximum (all inputs set, with supply to the sensors via
clock supplies OUT_T1 and OUT_T2)
“Technical data and ordering data” on page 75
.