12.2 Technical data
Dimensions (nominal sizes in mm)
Width
14.9 mm
Height
62.2 mm
Depth
62 mm
General data
Color
Zinc yellow, RAL 1018
Weight
36 g
Operating mode
PROFIsafe 2.4, PROFIsafe 2.6.1
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C … 85 °C
Permissible humidity (operation)
5% ... 95% (non-condensing)
Permissible humidity (storage/transport)
5% ... 95% (non-condensing)
Air pressure (operation)
70 kPa ... 108 kPa
Air pressure (storage/transport)
66 kPa ... 108 kPa
Degree of protection
IP20
Degree of protection at installation location
IP54, minimum
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Overvoltage category
II (IEC 60664-1)
Pollution degree
2 (EN 60664-1)
Mounting position
Any
Maximum altitude
≤3000 m (above sea level)
Air clearances and creepage distances
IEC 60664-1
Recommendation:
Do not use the Smart Element in an atmosphere that contains corrosive gas.
Connection data: I/O
Connection method
Push-in connection
Conductor cross section solid/flexible
0.25 mm² ... 1.5 mm²/0.25 mm² ... 1.5 mm²
Conductor cross section [AWG]
24 ... 16
Stripping length
8 mm
Note
Note the specification in Section “Conductor cross sections,
and stripping and insertion lengths”.
Interface: Smart Element interface
Number
1
Connection method
Card edge connector