AXL SE PSDI8/3
26 / 84
PHOENIX CONTACT
108928_en_02
4.2
Setting the safety address
4.2.1
Address assignment via DIP switch
Setting the address prior
to mounting
A 10-pos. DIP switch is located on the side of the Smart Element.
The DIP switch is used to set the PROFIsafe address (F-Address).
Set the address via the DIP switch
prior
to mounting.
PROFIsafe addresses 1 to 1022 (1
hex
to 3FE
hex
) are permitted.
Addresses 0 and 1023 (3FF
hex
) are
invalid
addresses.
By default, the address is set to 0 (invalid address).
Figure 4
-
1
DIP switch
MSB
The most significant bit (MSB) has the highest value.
LSB
The least significant bit (LSB) has the lowest value.
The set address is only applied on power-up. If the address is adjusted during operation,
the Smart Element responds with an error message.
Table 4
-
1
DIP switch for PROFIsafe address