AXL SE PSDI8/3
52 / 84
PHOENIX CONTACT
108928_en_02
7.3
Two-channel equivalent assignment of the safe
inputs
7.3.1
Cross-circuit monitoring enabled, supply through OUT_T1
and OUT_T2
Figure 7
-
5
2-channel equivalent assignment of inputs,
supply through OUT_T1 and OUT_T2 (both clocked)
Basic specifications
Typical parameterization
S1, S2
OUT_T1,
OUT_T2
Switching elements
Supply through OUT_T1
and
OUT_T2
S1
IN _C 1
0 H
OUT_T1
S2
IN _C 2
0 H
OUT_T2
Sensor
2-channel equivalent with cross-circuit monitoring
Sensor supply
Internally through clock output OUT_T1
and
OUT_T2 (both clocked)
Achievable
SIL/SILCL/Cat./PL
SIL 3/SILCL 3/Cat. 4/PL e
Parameterization
Parameterized as/value range
Comment
Input xx, channel 1/channel 2
Assignment
Used, 2-channel equivalent
Mandatory setting
Filter time (t
Filter
)
3 ms
Application-specific
Symmetry
100 ms
Application-specific
Start inhibit due to symmetry
violation
Enabled
Application-specific
Cross-circuit monitoring
Enabled
Mandatory setting