Appendix
108928_en_02
PHOENIX CONTACT
81 / 84
A Appendix
A 1
Diagnostic messages for parameter errors for
PROFIsafe
Table A
-
1
F-Parameter parameter errors
Error code
Error cause
Remedy
dec
hex
64
40
The parameterized F_Destination_Address does not
match the PROFIsafe address set on the module (F-
Module).
Make sure that the PROFIsafe address of the
module and the value in F_Destination_Ad
-
dress are the same.
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct the value.
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct the value.
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
Correct the value.
72
48
Device-specific diagnostics.
73
49
Save i-Parameter watchdog time exceeded.
74
4 A
Restore i-Parameter watchdog time exceeded.
75
4B
Invalid F_iParCRC.
Correct the value.
79
4F
Non-specified (unknown) error
Table A
-
2
i-Parameter parameter errors
AddValue
(hex)
Error cause
Remedy
03F2
iPar_CRC is incorrect.
Check the i-Parameters. Repeat the calcula
-
tion.
03FB
PST_Device_ID is incorrect.
Contact Phoenix Contact.