State evaluation
The Smart Element evaluates the states of the inputs and transmits the result to the control
-
ler.
The following values are transmitted in the process data image of the safe inputs:
– “0” if a “0” signal is present at at least one of the two inputs
or
an error has been detected
– “1” if a “1” signal is present at both inputs
and
no error has been detected and the con
-
ditions are met for a change in state according to
Example of correct and incorrect signal change
Figure 6
-
1
Correct signal change
Figure 6
-
2
Error during signal change
Key:
, the following condition has not been met: both signals must have been in state
“0” before the change in state from “0” to “1”. A diagnostic message is generated because
the condition is not met.
IN0_CH1
Signal sequence at input 0, channel 1
IN0_CH2
Signal sequence at input 0, channel 2
IN0 (CH1/CH2)
Safety-related signal for 2-channel input 0, channel 1, and channel 2 at
the controller
1
0
1
0
1
0
IN0_C 1
H
IN0_C 2
H
I 0 (C 1/C 2)
N
H
H
1
0
1
0
1
0
IN0_C 1
H
IN0_C 2
H
IN0 (C 1/C 2)
H
H
For examples and further information on error detection and error messages, please refer
to the following sections:
–
“Connection examples of safe inputs” on page 45
–