10.20 16 Depth Protection
NOTE
The parameters in this group are only active if a smart card is installed.
Depth protection uses terminals B13, B14 or C13, C14 on the smart card.
16A – Depth Trip Level
Range:
0 – 1000
Default:
5
Description:
Sets the trip point for depth protection.
16B – Depth Reset Level
Range:
0 – 1000
Default:
10
Description:
Sets the level for the VersiStart p III to auto-reset a depth trip.
16C – Depth Start Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay before a depth protection trip can occur. The delay is
counted from the time a start signal is received. The depth input is
ignored until the start delay has elapsed.
16D – Depth Response Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay between the depth passing the depth protection trip
level, and the soft starter tripping.
10.21 17 Thermal Protection
NOTE
The parameters in this group are only active if a smart card is installed.
17A – Temperature Sensor Type
Options:
None (default)
PT100
Description:
Selects which type of sensor is associated with the temperature
sensor input on the smart card.
17B – Temperature Trip Level
Range:
0° – 240°
Default:
40°
Description:
Sets the trip point for temperature protection. Use parameter 10B
Temperature Scale
to configure the temperature scale.