VersiStart p III
96
11.2 Smart Card - Level Controlled Pump Activation
The VersiStart p III smart card can be used to control start/stop activation of the
starter, based on information from external inputs.
In this example, the VersiStart p III controls a pump which fills a tank, with
maximum and minimum water levels. A pressure sensor is used to monitor the
level of water in the tank and trigger the pump to fill the tank when water drops
below the minimum level, and shut off the pump when the maximum water level is
reached.
A three-way selector switch allows the user to override sensor-based control, and
manually start or stop the motor.
10
11
12
A3
A1
A2
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
13
14
34
33
K1
K1
F1
D
IGI
T
A
L
I
NP
UT
S
4/
20m
A
I
NP
UT
S
R
TD
C24
C33
C34
C43
C13
C14
C23
C44
B14
B13
B23
B24
B33
B34
R2
R1
R3
1
A
B
C
A
B
C
2
3
4
17885.B
7
8
5
6
1
Digital inputs
K1
Main contactor
A
Manual start
10, 11
Reset input
B
Manual stop
11, 12
Start/stop input
C
Automatic operation
(level-controlled)
13, 14
Programmable input A
(set = Command Override: Digital)
2
Control voltage
33, 34
Main contactor output
3
Three-phase supply
B33, B34 Flow protection
4
Smart card
B23, B24 Pressure or depth based control
5
Maximum water level
6
Flow sensor
7
Pressure sensor
8
Minimum water level
Parameter settings:
•
Parameter 1A
Command Source
: select 'Smart Card'.
•
Parameter 7A
Input A Function
: select 'Command Override: Digital'.
•
Parameters 12A~12Q Pump Input Configuration: Set as required.
•
Parameters 13A~13D Flow Protection: Set as required.
•
Parameters 15A~15E Pressure Control: Set as required.