69
VersiStart p III
Description:
Sets the level of the kickstart current.
3H – Jog Torque-2
Range:
20% - 100%
Default:
50%
Description:
Sets the current limit for jog operation.
3I – Stop Mode-2
Options:
Coast To Stop
TVR Soft Stop (default)
Adaptive Control
DC Brake
Soft Brake
Description:
Selects the stop mode.
3J – Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
1 second
Description:
Sets the time for soft stopping the motor using timed voltage ramp or
Adaptive Control.
If a main contactor is installed, the contactor must remain closed until
the end of the stop time. Use the main contactor output (33, 34) to
control the main contactor.
3K – Adaptive Stop Profile-2
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description:
Selects which profile the VersiStart p III will use for an Adaptive
Control soft stop.
3L – Adaptive Control Gain-2
Range:
1%~200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting affects both
starting and stopping control.
3M – Multi Pump-2
Options:
Single Pump (default)
Manifold Pump
Description:
Adjusts the performance of adaptive control to suit installations with
multiple pumps connected to a common outlet manifold.
3N – Start Delay-2
Range:
0:00 - 3:20 (minutes:seconds)
Default:
0 second
Description:
Sets a delay after the starter receives a start command, before it
starts the motor.
3O – DC Brake Torque-2
Range:
20% - 100%
Default:
20%