10.19 15 Pressure Control
Pressure control use terminals B23, B24 on the smart card.
NOTE
The parameters in this group are only active if a smart card is installed.
15A – Pressure Control Mode
Options:
Off (default)
The VersiStart p III will not use the pressure
sensor to control soft starting.
Falling Pressure
Start
The VersiStart p III will start when the pressure
drops below the level selected in parameter 15B
Start Pressure Level
.
Rising Pressure
Start
The VersiStart p III will start when the pressure
rises above the level selected in parameter 15B
Start Pressure Level
.
Description:
Selects how the VersiStart p III will use data from the pressure sensor
to control the motor.
15B – Start Pressure Level
Range:
1 – 5000
Default:
5
Description:
Sets the pressure level to trigger the VersiStart p III to perform a soft
start.
15C – Start Response Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay between the pressure passing the pressure control start
level, and the VersiStart p III performing a soft start.
15D – Stop Pressure Level
Range:
0 – 5000
Default:
10
Description:
Sets the pressure level to trigger the VersiStart p III to stop the motor.
15E – Stop Response Delay
Range:
00:00:10 – 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay between the pressure passing the pressure control stop
level, and the VersiStart p III stopping the motor.