VersiStart p III
58
10 Programmable Parameters
10.1 Programming Menu
The Programming Menu lets you view and change programmable parameters that
control how the VersiStart p III operates.
To open the Programming Menu, press the
MENU/ENTER
button while viewing the
monitoring screens.
10.2 Altering Parameter Values
To change a parameter value:
•
scroll to the appropriate parameter in the Programming Menu and press
ENTER/MENU
to enter edit mode.
•
to alter the parameter setting, use the and buttons. Pressing or
once will increase or decrease the value by one unit. If the button is held for
longer than five seconds, the value will increase or decrease at a faster rate.
•
to save changes, press
STORE
. The setting shown on the display will be
saved and the keypad will return to the parameter list.
•
to cancel changes, press
EXIT
. The keypad will ask for confirmation, then
return to the parameter list without saving changes.
10.3 Adjustment Lock
You can prevent users from altering parameter settings by turning on the
adjustment lock (parameter 10G
Adjustment Lock
).
If a user attempts to change a parameter value when the adjustment lock is active,
an error message is displayed:
Access Denied
Adj Lock is On
10.4 Parameter List
Parameter Group
Default Setting
1
Motor Details
1A
Command Source
Digital Input
1B
Motor Full Load Current
Model dependent
1C
Locked Rotor Time
00:10 (mm:ss)
1D
Locked Rotor Current
600%
1E
Motor Service Factor
105%
2
Motor Start/Stop
2A
Start Mode
Constant Current
2B
Start Ramp Time
00:10 (mm:ss)
2C
Initial Current
200%
2D
Current Limit
350%
2E
Adaptive Start Profile
Constant Acceleration
2F
Kickstart Time
000 ms