VersiStart p III
70
Description:
Sets the amount of brake torque the VersiStart p III will use to slow
the motor.
3P – DC Brake Time-2
Range:
0:01 - 0:30 (minutes:seconds)
Default:
1 second
Description:
Sets the duration for DC injection during a braking stop.
3Q – Brake Current Limit-2
Range:
100% - 600% FLC
Default:
250%
Description:
Sets the current limit for soft brake.
3R – Soft Brake Delay-2
Range:
400 - 2000 milliseconds
Default:
400 milliseconds
Description:
Sets the time the soft starter will wait after a stop signal is received,
before it begins to supply braking current to the motor. Set to allow
time for K1 and K2 to switch.
10.8 4 Auto-Start/Stop
The VersiStart p III can be configured to automatically start and/or stop the motor
once per day. For auto-start/stop to operate:
•
parameter 4A
Auto-Start/Stop Mode
must be set to 'Enable'
•
parameter 1A
Command Source
must be set to 'Clock'
•
the reset input must be closed
•
the start input (11, 12) must be active. This allows the VersiStart p III to be
stopped via the digital inputs in an emergency.
•
parameters 4B ~ 4V: Set as required.
4A – Auto-Start/Stop Mode
Options:
Disable (default)
Enable
Description:
Enable or disable auto-start/stop operation.
4B – Sunday Mode
Options:
Start/Stop Disable
(default)
Disables auto-start/stop control. Any times
scheduled in parameters 4C or 4D will be
ignored.
Start Only Enable
Enables auto-start control. Any auto-stop times
scheduled in parameter 4D will be ignored.
Stop Only Enable
Enables auto-stop control. Any auto-start times
scheduled in parameter 4C will be ignored.
Start/Stop Enable
Enables auto-start and auto-stop control.
Description:
Enables or disables auto-start/stop for Sunday.
4C – Sunday Start Time
Range:
00:00 - 23:59
Default:
00:00