89
VersiStart p III
12N – Depth Sensor Type
Options:
None (default)
Switch
Analog
Description:
Selects which type of sensor is associated with the depth sensor input
on the smart card.
12O – Depth Units
Options:
metres (default)
feet
Description:
Selects which units the sensor will use to report the measured depth.
12P – Depth at 4 mA
Range:
0 – 1000
Default:
0
Description:
Calibrates the soft starter to the 4 mA (0%) level of the depth sensor
input.
12Q – Depth at 20 mA
Range:
0 – 1000
Default:
0
Description:
Calibrates the soft starter to the 20 mA (100%) level of the depth
sensor input.
10.17 13 Flow Protection
NOTE
The parameters in this group are only active if a smart card is installed.
Flow protection uses terminals B33, B34 or C23, C24 on the smart card.
13A – High Flow Trip Level
Range:
0 – 5000
Default:
0
Description:
Sets the trip point for high flow protection.
13B – Low Flow Trip Level
Range:
1 – 5000
Default:
5
Description:
Sets the trip point for low flow protection.
13C – Flow Start Delay
Range:
00:00:50 - 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay before a flow protection trip can occur. The delay is
counted from the time a start signal is received. The flow level is
ignored until the start delay has elapsed.
13D – Flow Response Delay
Range:
00:00:10 - 30:00:00 mm:ss:ms
Default:
0.5 seconds
Description:
Sets a delay between the flow passing the high or low flow trip levels,
and the soft starter tripping.