VersiStart p III
28
5.4 Outputs
Output Terminals
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
B4 B5 10 11 12 13 14 15 21 22
33 34 41 42 44 53 54
A3 A1 A2
33 34 41 42 44 53 54
B4 B5 10 11 12 13 14 15
21 22
21, 22
Analog output
33, 34
Main contactor output
41, 42, 44 Relay output A (default = Run)
53, 54
Relay output B (default = Run)
Analog Output
The VersiStart p III has an analog output, which can be connected to associated
equipment to monitor motor performance.
The operation of the analog output is controlled by parameters 9A ~ 9D.
Main Contactor Output
The main contactor output (33, 34) closes as soon as the soft starter receives a
start command and remains closed while the soft starter is controlling the motor
(until the motor starts a coast to stop, or until the end of a soft stop). The main
contactor output will also open if the soft starter trips.
CAUTION
Some electronic contactor coils are not suitable for direct switching with
PCB mount relays. Consult the contactor manufacturer/supplier to confirm
suitability.
Programmable Outputs
The programmable outputs (41, 42, 44 and 53, 54) can report the status of the
starter, or can be used to control associated equipment.
The operation of the programmable outputs is controlled by parameters 8A ~ 8F.