25
VersiStart p III
5
Installation
WARNING
Do not apply mains voltage to the starter until all wiring is complete.
WARNING
Always apply control voltage before (or with) mains voltage.
5.1 Command Source
The VersiStart p III can be started and stopped via the digital inputs, remote
keypad, communication network, smart card or scheduled auto-start/stop. The
command source can be set via the Setup Tools, or using parameter 1A
Command
Source
.
5.2 Basic Setup
Setup Procedure Overview
1. Mount the soft starter (refer to
Physical Installation
on page 15 for details).
2. Connect control wiring (refer to
Input Terminals
on page 26 for details).
3. Apply control voltage to the starter.
4. Configure your application:
1. Press
MENU
to open the Menu.
2. Press
ENTER/MENU
to open the Quick Setup menu.
3. Scroll through the list to find your application, then press
ENTER/MENU
to
begin the configuration process (refer to
Quick Setup
on page 33 for details).
5. If your application is not listed in Quick Setup:
1. Press
EXIT
to return to the Menu.
2. Use to scroll to Main Menu and press
ENTER/MENU
.
3. Scroll to Motor Details and press
ENTER/MENU
, then press
ENTER/MENU
again to edit parameter 1B
Motor Full Load Current
.
4. Set parameter 1B to match the motor's full load current (FLC).
5. Press
ENTER/MENU
to save the setting.
6. Close the Menu by pressing
EXIT
repeatedly.
7. (Optional) Use the built-in simulation tools to check that the control wiring is
connected correctly (refer to
Run simulation
on page 35).
8. Power off the soft starter.
9. Connect the motor cables to starter output terminals 2/T1, 4/T2, 6/T3.
10. Connect mains supply cables to starter input terminals 1/L1, 3/L2, 5/L3 (refer to
Power Terminations
on page 30).
The soft starter is now ready to control the motor.