VersiStart p III
26
5.3 Inputs
CAUTION
The control inputs are powered by the soft starter. Do not apply external
voltage to the control input terminals.
NOTE
Cables to the control inputs must be segregated from mains voltage and
motor cabling.
Input Terminals
B4 B5 10 11 12 13 14 15
21 22
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
B4 B5 10 11 12 13 14 15 21 22
33 34 41 42 44 53 54
A3 A1 A2
B4, B5 Motor thermistor input
10, 11
Reset input
11, 12
Start/stop input
13, 14
Programmable input A
(default = Input Trip (N/O))
13, 15
Programmable input B
(default = Input Trip (N/O))
USB port
Summary of Contents for VersiStart p III 105