4.13 UL Coordination with Short Circuit Protection Devices
Standard Fault Short Circuit Current Ratings
Suitable for use on a circuit capable of delivering not more than the stated level of
amperes (symmetrical rms, refer ##1 in table), 600 VAC maximum.
•
Maximum fuse rating (A) – Standard fault short circuit current
Model
Nominal Rating (A)
3 cycle short cct rating
@600 VAC ##1 †
VS p III 24
24
5 kA
VS p III 42
42
VS p III 52
52
10 kA
VS p III 64
64
VS p III 69
69
VS p III 105
105
VS p III 115
120
VS p III 135
135
VS p III 184
184
18 kA
VS p III 200
225
VS p III 229
229
VS p III 250
250
VS p III 352
352
VS p III 397
397
VS p III 410
410
30 kA
VS p III 550
550
VS p III 580
580
† Suitable for use in a circuit with the prospective current noted, when protected by
any Listed fuses or Listed circuit breakers sized according to the NEC.