5.6 Power Terminations
The power input and output terminals for VersiStart P are at the bottom of the unit.
•
Models VS p III 24~VS p III 135 use cage clamps.
•
Models VS p III 184~VS p III 580 use busbars.
NOTE
Some units use aluminium busbars. When connecting power terminations,
we recommend cleaning the surface contact area thoroughly (using an
emery or stainless steel brush) and using an appropriate jointing compound
to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 ºC or higher.
VS p III 24~VS p III 135
0
5
9
6
6
.E
Cable size:
6-70 mm
2
(AWG 10-2/0)
Torque: 4 Nm (2.9 ft-lb)
Torx T20 x 150
Flat 7 mm x 150
11
29
0
.A
14 mm (0.55 inch)
VS p III 184~VS p III 250
VS p III 352~VS p III 580
19 Nm (14.0 ft-lb)
66 Nm (49.0 ft-lb)
6 mm
20 mm
9 mm
(M8)
17045.
A
6 mm
34 mm
13 mm
(M12)
17047.
A
NOTE
If the installation requires large diameter cables, it is possible to complete
each termination with two smaller cables, one on each side of the busbar.
UL Compliant Installation
For models VS p III 184 to VS p III 580 to be UL compliant, you must use the
recommended pressure terminal/connector.
Model
Recommended lugs part No.
VS p II 184
VS p II 200
OPHD 185-10
VS p II 229
VS p II 250
VS p II 352
VS p II 397
OPHD 150-12
VS p II 410
VS p II 550
OPHD 240-12
VS p II 580