13-5
Applications
650G AC Drive
Application 2: Auto/Manual Control
Two Run inputs and two Setpoint inputs are provided. The Auto/Manual switch selects which pair of inputs is active.
The Application is sometimes referred to as Local/Remote.
Manual
User Relay
10
9
8
7
6
5
4
3
2
1
RL1A
RL1B
13
12
11
WIRE
SINGLE
STARTING
DIN7 (ENCB)
DIN6 (ENCA)
DIN5
DIN4/DOUT2
DIN3
SELECT
24V = run forward
DIN2
REMOTE REVERSE 0V = remote forward, 24V = remote reverse
DIN1
MANUAL RUN
24V = run forward
+24V
AOUT
RAMP OUTPUT
+10V REF
AIN2
AUTO SETPOINT
AIN1
MANUAL SETPOINT
0V
DOUT3 (relay)
24V
+10V REF
0V
not used
Control
Terminal
NOT COAST STOP
24V = coast to stop, 0V = drive may run
AUTO RUN
24V = run forward
Setpoint
Auto
Setpoint
DEMAND (0V = 0%, 10V = 100%)
4mA = 0%, 20mA = 100%
0V = 0%, 10V = 100%
RELAY SOURCE
HEALTH i.e. 0V = not healthy
= 0
= 3
= 1
= 1
default source
A or V
= 4-20mA
not used