![Parker 650G series Product Manual Download Page 101](http://html.mh-extra.com/html/parker/650g-series/650g-series_product-manual_755633101.webp)
Technical Specifications
9-3
650G AC Drive
Environmental Details
Operating Temperature
HEAVY DUTY
NORMAL DUTY
Operating temperature is defined as the ambient temperature to the immediate
surround of the drive, when the drive and other equipment adjacent to it is operating
at worst case conditions.
0
C to 45
C (0
C to 40
C with top cover fitted), derate up to a maximum of 50
C
0
C to 40
C (0
C to 35
C with top cover fitted), derate up to a maximum of 50
C
Output power is derated linearly at 2% per degree centigrade for temperature
exceeding the maximum rating ambient for the drive.
Storage Temperature
-25
C to +55
C
Shipping Temperature
-25
C to +70
C
Product Enclosure Rating
Frames C, D, E & F
Wall Mounted
(top cover must be fitted)
IP40 - top cover surface (Europe)
IP20 - remainder of surfaces (Europe)
UL (c-UL) Type 1 (North America/Canada)
Cubicle Mounted
(without top cover fitted)
IP20
UL (c-UL) Open Type (North America/Canada)
Through-panel Mounted
(without top cover fitted)
IP20
UL (c-UL) Open Type (North America/Canada)
Frames 1, 2 & 3 IP20 (UL Open Type) suitable for cubicle mount only
Cubicle Rating
Cubicle to provide 15dB attenuation to radiated emissions between 30-100MHz. It
must also require a security tool for opening
Altitude
If >1000 metres (3300 feet) above sea level, derate Motor Power Rating by 1% per
100 metres (330 feet) to a maximum of 2000m (6561 feet)
Humidity
Maximum 85% relative humidity at 40
C non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Climatic Conditions
Class 3k3, as defined by EN50178 (1998)
Vibration
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Safety
Overvoltage Category Overvoltage Category
III
(numeral defining an impulse withstand level)
Pollution Degree Pollution Degree
II
(non-conductive pollution, except for temporary condensation)
Pollution Degree
III
(dirty air rating for through-panel mounted parts)
Europe When fitted inside a cubicle, or when wall-mounted and the top cover is firmly screwed in
position, this product conforms with the Low Voltage Directive 2006/95/EC to show compliance.
North America/Canada Without the top cover fitted, complies with the requirements of UL508C as an open-type drive.
When the top cover is fitted, complies with the requirements of UL508C as Type 1 Enclosed (for
direct wall mounting applications) when specified with Model Number Block 6 (Frame B) or
Modle Number Block 4 (Frame C, D, E, F) designation xx20 or xx21 only.
www.comoso.com