![Parker 650G series Product Manual Download Page 62](http://html.mh-extra.com/html/parker/650g-series/650g-series_product-manual_755633062.webp)
5-4
The Keypad
650G AC Drive
How To Change a Parameter Value
You can change the values of parameters stored in the
and
menus. Refer to Chapter
6: “Programming Your Application” – Configurable Parameters for further information.
View the parameter to be edited and press
to display the parameter’s value.
Select the digit to be changed (pressing the
key moves the cursor from right to left).
Use the
keys to adjust the value. Hold the key momentarily to adjust the value
marginally, or hold the key to make rapid changes; the rate of change varies with the time
held.
Press
to return to the parameter display. The new value is stored.
Special Menu Features
Resetting to Factory Defaults (2-button reset)
Power-up the drive whilst holding the keys as
shown to return to factory default settings.
This loads Application 1. Then press the
key.
Changing the Drive Operating Frequency
Power-up the drive whilst holding the keys as
shown to display the Engineers Menu.
IMPORTANT:
This menu contains sensitive parameters that
can dramatically alter the running of the drive.
This displays parameter
E
0.01. Press the
key to navigate to
E
0.02. Press the
key to
edit the parameter: 0 = 50Hz (default), 1 = 60Hz. Select the required frequency then press the
key.
Power-down the drive. No permanent change has been made to the drive at this point. To save
the change to parameter
E
0.02, you must now perform a 2-button reset (as above). Please note
that this will return the drive to its factory default settings for the selected default frequency.
Selecting Local or Remote Control
The drive can operate in one of two ways:
Remote Control:
Allowing access for application programming using digital and
analog inputs and outputs
Local Control:
Providing local control and monitoring of the drive using the
Keypad
Local control keys are inactive when Remote Control is selected.
In Remote Control, the drive uses a remote setpoint. In Local Control, it uses the Local Setpoint
parameter whose value is adjusted on the MMI.
Note:
You can only change between Local and Remote Control when the drive is “stopped”,
and either
or the Local Setpoint is displayed.
Remote to Local Control:
Hold down the keys opposite:
Power-up the drive, continue
to hold for at least 1 second
HOLD
Hold down the keys opposite:
Power-up the drive, continue
to hold for at least 1 second
HOLD
Hold this key down until
the display shows
REMOTE
LOCAL
Hold this key down until
the display spells
Release the key to display
the Local Setpoint
www.comoso.com