Programming Your Application
6-4
650G AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
R/L RESET VALUE The value the output is set to when Reset is TRUE,
when DIN4 (terminal 10) is 24V in Application 4
-100.00 to 100.00% 0.00%
Parameters
P
501 and
P
506 are visible in the PAR menu when Application 5 is selected in parameter
P
1
PI P GAIN
The PI proportional gain
0.00 to 100.00
0.10
PI I GAIN
The PI integral gain
0.00 to 100.00
1.00
PID D GAIN
F
The PID derivative gain
0.00 to 100.00
0.00
PID D FILTER TC
F
In order to help attenuate high frequency noise on
the derivative term, a first order lag has been
provided. This parameter determines the filter time
constant.
0.05 to 10.00s
0.05s
PID FEEDBACK
GAIN
F
A multiplier applied to the feedback signal of the
PID
-10.00 to 10.00
1.00
PID LIMIT
F
Determines the maximum positive and negative
excursion (Limit) of the PID output
0.00 to 300.00%
300.00%
PID SCALING
F
This parameter represents an overall scaling factor
which is applied after the PID positive and negative
limit clamps
-3.0000 to 3.0000
1.0000
PID ERROR
F
The result of SETPOINT - FEEDBACK x FEEDBACK
GAIN
—.xx %
—.xx%
PID OUTPUT
F
The output of the PID function block
—
.xx %
—
.xx %
Parameters
P
901 and
P
908 are visible in the PAR menu when there are corresponding entries in the CUSTOM MENU block.
CUSTOM 1
Select a parameter to be displayed in the PAR
Menu by entering the Tag Number for the
parameter using DSE (or other suitable
programming tool). Eight parameters can be
entered into the menu. CUSTOM 1 is the first of
the new parameters in the menu, CUSTOM 2 is
the second of the new parameters in the menu,
and so on. These parameters contained in P901 to
P908 will appear at the bottom of the parameter
list for the PAR Menu.
Enter 0 to leave a position in the menu unused.
0 to 1655
0
CUSTOM 2
As
P
901
0 to 1655
0
CUSTOM 3
As
P
901
0 to 1655
0
CUSTOM 4
As
P
901
0 to 1655
0
CUSTOM 5
As
P
901
0 to 1655
0
CUSTOM 6
As
P
901
0 to 1655
0
CUSTOM 7
As
P
901
0 to 1655
0
CUSTOM 8
As
P
901
0 to 1655
0
SET::CTRL Menu
CONTROL MODE This parameter contains the main method of
motor control used by the drive
0=VOLTS/HZ
1=SENSORLESS VEC
0
NAMEPLATE RPM
M
This parameter contains the motor nameplate full-
load rated speed. This is the motor speed in rpm
at base frequency minus full load slip
0.1 to 30000.0 RPM product
code
dependent
FLY-CATCH
ENABLE
VF
Enables flycatching in Volts/Hz control mode when
TRUE. Allows the drive to catch a spinning load.
0=FALSE
1=TRUE
0
FLY-CATCH
ENABLE
SV
Enables flycatching in Sensorless Vector control
mode when TRUE. Allows the drive to catch a
spinning load.
0=FALSE
1=TRUE
0