Installing the Drive
3-18
650G AC Drive
Power Terminal Description
Terminal Description
Function
Range
200V 1-Phase
200V/400V 3-Phase
TH1A Thermistor
Connection to motor
thermistor
It is good practice to protect motors by fitting temperature
sensitive resistors. A typical resistance (up to a reference
temperature of 125
C) is 200
, rising rapidly to 2000
above
this temperature. Connect devices in series between TH1A and
TH1B. Link the terminals if temperature sensors are not used.
TH1B Thermistor
Connection to motor
thermistor
Reference
Terminal
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
L1 *
Power Input Single and three
phase live
connection
220/240V ac ±10%
rms with respect to
L2/N. 50-60Hz (IT/TN)
220/240V or 380/460V ac ±10%
rms with respect to L2, L3 phase-to-
phase. 50-60Hz (IT/TN)
L2/N *
L2
Power Input Single phase neutral
(or L2 three phase
live connection)
220/240V ac ±10%
with respect to L1. 50-
60Hz (IT/TN)
220/240V or 380/460V ac ±10%
with respect to L1, L3. 50-60Hz
(IT/TN)
L3
Power Input Three phase live
connection
Not applicable
220/240V or 380/460V ac ±10%
with respect to L1, L2. 50-60Hz
(IT/TN)
DC-
Power Input Common bus supply Not applicable
DC+ Power
Input/
Dynamic
Brake
Common bus
supply/external
brake resistor
Not applicable
See “Internal Dynamic Brake Switch”
table
DBR Dynamic
Brake
Connection to
external brake
resistor
Not applicable
See “Internal Dynamic Brake Switch”
table
M1/U
M2/V
M3/W
Motor
Outputs
Connection for
motor
Motor rated at:
0 to 220/240V ac
0 to 240Hz
Motor rated at:
0 to 220/240V or 0 to 380/460V ac
0 to 240Hz
Reference
Terminal
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
Terminal Block Acceptance Sizes
Wire sizes for Europe should be chosen with respect to the operating conditions and your local National
Electrical Safety Installation Requirements. Local wiring regulations always take precedence. For North
American UL wire sizes refer to Chapter 10: “Certification for the Drive” - Requirements for UL
Compliance.
Product Code
Power Terminals
(minimum/maximum acceptance for aperture)
Control Terminals
including Thermistor Terminals
Frame 1 - 2
0.75 mm
2
/ 2.5 mm
2
12AWG 2.5
mm
2
Frame 3
6.0 mm
2
/ 2.5 mm
2
10AWG 2.5
mm
2
Frame C
0.75 mm
2
/ 10mm
2
(*16mm
2
) 2.5
mm
2
Frame D (15-22kW)
2.5 mm
2
/ 16mm
2
(* 25mm
2
) 2.5
mm
2
Frame D (30/18.5kW)
2.5 mm
2
/ 25mm
2
(* 35mm
2
) 2.5
mm
2
Solid
Stranded
Frame E
16 mm
2
/ 50mm
2
25
mm
2
/ 50mm
2
(* 70mm
2
) 2.5
mm
2
Frame F
25 mm
2
/120mm
2
35
mm
2
/ 95mm
2
(*120mm
2
) 2.5
mm
2
Note: The standard Frame E and Frame F terminals are not intended for flat busbar. A Power Terminal adaptor is
available to enable wiring with flat busbar, part number BE465483.
* The larger wire sizes can be used provided a crimp is fitted to the wire