Technical Specifications
9-5
650G AC Drive
Electrical Ratings
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Maximum Motor dv/dt = 10,000V/
s. This can be reduced by adding a motor choke in series
with the motor. Contact Parker SSD Drives for recommended choke details.
Local wiring regulations always take precedence. Select cable rated for the drive.
The supply must be protected with a fuse (or Type B RCD) rated to the supply cable.
FRAME 1 : 1-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
Input Current @ 5kA
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
Surge Current
peak/rms for 10ms (A)
(A)
0.25/0.3 19/12 4.2
1.5
26
0.37/0.5 19/12 6.2
2.2
32
0.55/0.75 20/14 7.9
3.0
41
0.75/1.0 22/15 10.5
4.0
52
FRAME 2 : 1-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
Input Current @ 5kA
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
Surge Current
peak/rms for 10ms (A)
(A)
1.1/1.5
24/17
13.8 5.5
65
1.5/2.0
25/18
16.0 7.0
82
FRAME 2 : 3-Phase (IT/TN), 400V
Drive
Power
(kW/hp)
Input Current @ 10kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
0.37/0.5 2.5
1.5
26
0.55/0.75 3.3
2.0
32
0.75/1.0 4.1
2.5
40
1.1/1.5 5.9
3.5
55
1.5/2.0 7.5
4.5
61
2.2/3.0 9.4
5.5
70
FRAME 3 : 1-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
Input Current @ 7.5kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
2.2/3.0 22.0
9.6
112
FRAME 3 : 3-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
Input Current @ 7.5kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
2.2/3.0 14.3
9.6
103
3.0/4.0 18.1
12.3
133
4.0/5.0 23.1
16.4
180
FRAME 3 : 3-Phase (IT/TN), 400V
Drive
Power
(kW/hp)
Input Current @ 10kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power
Loss
(W)
3.0/4.0 11.1
6.8
80
4.0/5.0 13.9
9.0
100
5.5/7.5 18.0
12.0
136
7.5/10.0 23.6
16.0
180