![Parker 650G series Product Manual Download Page 109](http://html.mh-extra.com/html/parker/650g-series/650g-series_product-manual_755633109.webp)
Technical Specifications
9-11
650G AC Drive
External AC Supply (RFI) Filters
Drive
Filter Part No.
Motor Power
(kW/Hp)
Phase Watt
Loss
(W)
Fault
Leakage
Current
(mA)
Current
(A)
Maximum
Supply
Voltage
(V)
EMC
Performance
Class
Maximum
Motor
Cable
Length
(m)
Frame C
CO467842U044 : 500V
(IT/TN Filter)
7.5-18.5/10-25
normal duty
3 14 80 35 500
B
50
Frame D
CO467842U084 : 500V
(IT/TN Filter)
18.5-37/25-50
normal duty
3 18 86 64 500
B
50
Frame E
CO467842U105 : 500V
(IT/TN Filter)
37-55/50-75
normal duty
3 50 200 124 500
B
50
Frame F
CO467842U215 : 500V
(IT/TN Filter)
75-110/100-
150
normal duty
3 60 450 205 500
B
50
Filters suitable for 50-60Hz ±5%, switching frequency 3 & 6kHz
EMC Compliance Frames 1, 2 & 3
Standard EN 61800-3
Frame 1 & 2 :
1-Phase
Frames 2 & 3
1 & 3-Phase
Conducted
emissions
Table 14
First Environment
Category C1
Yes
(Maximum motor cable length: 25,m)
N/A
Conducted
emissions
Table 14
First Environment
Category C2
N/A
Yes
(Maximum motor cable length: 25,m)
Radiated
Emissions
Table 15
First Environment
Category C1
Yes
(When mounted inside the specified
cubicle. Control and motor cables must
be screened and correctly fitted with
glands where they exit cubicle. Control
0V must be connected to protective
earth/ground)
Yes
(When mounted inside the specified
cubicle. Control and motor cables must be
screened and correctly fitted with glands
where they exit cubicle. Control 0V must
be connected to protective earth/ground)
www.comoso.com