3-31
Installing the Drive
650G AC Drive
Encoder Connections
The drive is
only
suitable for use with single-ended encoders.
Take special care wiring the encoder to the drive due to the
low level of the signals.
All wiring to the drive should be made in screened cable. Use
cable with an overall screen and a screen over each individual
pair. To ensure compliance with the EMC Directive the overall
cable screen should be connected to the drive chassis.
Recommended cable (pairs individually screened):
Belden equivalent 8777
Parker SSD Drives Part Number CM052666
The drive will operate with 5-24V encoders. Provide the
correct supply for the encoder. Do not use the 10V or 24V
supply from the drive.
12
13
ENC A
ENC B
A
B
+
-/0V
supply
ENCODER
Drive
chassis
DRIVE
Encoder
supply
-/0V
0V
1
www.comoso.com