9-6
Technical Specifications
650G AC Drive
Electrical Ratings (230V Build Variant)
Power Supply = 220-240V ±10%, 45-60Hz
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Operation at 208V
10% (Frames C, D, E & F)
Nominal motor powers are reduced by 10% when operated at 208V
10%. Output currents
remain unchanged.
Model Number
Motor
Power
Output
Current
(A)
Input
Current
(A)
Heatsink
Power
Loss
(W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
FRAME C :
Input currents for kW ratings are at 230V 50Hz ac input. Supply short circuit rating 10kA.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232220-..
5.5kW
22
25
270
330
3
4000
7.5Hp
22
25
270
330
3
4000
650G-232280-..
5.5kW
28
33
290
350
3
6000
10Hp
28
33
290
350
3
6000
Normal Duty
(Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232220-..
7.5kW
28
31
330
390
3
4000
10Hp
28
31
330
390
3
4000
650G-232280-.. 11kW
42
49.3
500
560
3
6000
15Hp
42
49.3
500
560
3
6000
FRAME D :
Input currents for kW ratings are at 230V 50Hz ac input. Supply short circuit rating 10kA.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232420-.. 11kW
42
45
570
640
3
6000
15Hp
42
45
570
640
3
6000
650G-232540-.. 15kW
54
53
670
740
3
6000
20Hp
54
53
670
740
3
6000
650G-232680-..
18.5kW
68 65 850
920 3 6000
25Hp
68
65
850
920
3
6000
Normal Duty
(Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232420-.. 15kW
54
54
750
820
3
6000
20Hp
54
54
750
820
3
6000
650G-232540-..
18.5kW
68 65 850
920 3 6000
25Hp
68
65
850
920
3
6000
650G-232680-..
All values are the same as for Heavy Duty except for changes described by
parameter
P
12. Refer to Chapter 6 : "Programming Your Application"
FRAME E :
Input currents for kW ratings are at 230V 50Hz ac input. Prospective short circuit current 18kA.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232800-.. 22kW
80
91
800
920
3
18000
30Hp
80
91
800
920
3
18000
Normal Duty
(Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232800-.. 30kW
104
116
1050
1200
3
18000
40Hp
104
116
1050
1200
3
18000
FRAME F :
Input currents for kW ratings are at 230V 50Hz ac input. Prospective short circuit current 18kA.
Heavy Duty
(Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-233104-..
30kW 104 102 850
1100 3 100000
40Hp 104 102 850
1100 3 100000
650G-233130-.. 37kW
130
126
1100
1450
3
100000
50Hp
130
126
1100
1450
3
100000
650G-233154-.. 45kW
154
148
1200
1650
3
100000
60Hp
154
148
1200
1650
3
100000
Normal Duty
(Output Overload Motoring 110% for 30s, 125% for 0.5s short term rating)
650G-233104-.. 37kW
130
126
1150
1500
3
100000
50Hp
130
126
1150
1500
3
100000
650G-233130-.. 45kW
154
148
1350
1800
3
100000
60Hp
154
148
1350
1800
3
100000
650G-233154-.. 55kW
192
184
1600
2100
3
100000
75Hp
192
184
1600
2100
3
100000
www.comoso.com