3-27
Installing the Drive
650G AC Drive
External AC Supply EMC Filter
WARNING!
External filters are available for use with TN and IT supplies. Please check for
suitability in Chapter 9: “Technical Specifications” - External AC Supply (RFI) Filters.
Do not touch filter terminals or cabling for at least 3 minutes
after removing the ac supply.
Only use the ac supply filter with a permanent earth connection.
Mount the filter as close as possible to the drive.
Note:
Follow the cabling requirements given in Chapter 9 “Technical Specifications”
Refer to Chapter 10: “External AC Supply (RFI) Filters” for further information.
Footprint/Bookcase Mounting Filters for (Frame C, D, E & F)
These filters can be both footprint and bookcase mounted. They are suitable for wall or cubicle
mount, but the filter must be fitted with the appropriate gland box when wall mounted.
The filters for Frames C, D and E look similar. The Frame D filter drawing is given in the
following pages. Size variations for the frames are given in the table below.
The Frame F drawing and sizes are also supplied.
Filter
Description
Filter Part Number
Terminal
Block
Earth
Terminal
Gland
Mounting
Dimensions
Fixing
Centres
Weight
Frame C
500V IT/TN CO467842U044
10mm
2
5mm
4 x 4mm
400 x 178x 55mm
384 x
150mm
2.1kg
Gland Plate : BA467840U044
Frame D
500V IT/TN CO467842U084
25mm
2
6mm
4 x 4mm
513 x 233 x 70mm 495 x
208mm
4.2kg
Gland Plate : BA467840U084
Frame E
500V IT/TN CO467842U105
50mm
2
8mm
4 x 4mm
698 x 250 x 80mm 680 x
216mm
6.2kg
Gland Plate : BA467840U105
Frame F
500V IT/TN CO467842U215
95mm
2
8mm not
applicable
825 x 250 x
115mm
795 x
216mm
Gland Plate : Not applicable
www.comoso.com