7-5-9 Profile homing 5(3) (Z phase) [Type_Code: 35h(33h)]
This homing sequence uses Z phase as the trigger signal.
Type_Code Description
33h
When the detected POT/NOT and the direction of homing are the same direction,
Err94.2 (Homing error protection) will occur and cancel homing process.
35h
When the detected POT/NOT and the direction of homing are the same direction,
reverse operation will automatically start after deceleration and stop.
Define the 1st Z phase position in the homing direction as the home position.
Stop at the home and initialize the position information to set this position at 0.
Direction of homing can be set to either positive or negative through the setting of Pr.8.12 Profile homing mode setup.
Example: Type_Code = 35h, Pr.8.12 = 0 (Homing direction = positive direction trigger signal detection)
NOT ON
Z phase
Homing direction (positive direction)
Start area
Velocity 2
Velocity 2
POT ON
Velocity 1:
Pr.
8.13 (Profile homing velocity 1)
Velocity 2:
Pr.
8.14 (Profile homing velocity 2)
Ex.
See the next page.
Home position
Velocity 2
Ignore Z phase within reverse
direction limit (NOT).
Velocity 2
Velocity 2