148
External control
Troubles
Causes
Measures
Laser marker cannot be
controlled by the external
signal.
Laser marker is not in remote mode.
Press Remote switch on front of controller or enter
remote mode in a manner described in External
Control Manual.
The wiring between the laser marker
and the external control devices is
incorrect.
Check connections with external equipment for
mis-connection, disconnection or contact failure
due to any loose connector.
Check for continuity using tester or the like.
There are noises coming from
surrounding equipment.
Protect laser marker against noises as follows:
•
Securely ground frame ground (FG) of laser
marker or surrounding equipment.
•
Isolate power and signal lines from each other
if they have been routed in parallel.
•
Shield signal line.
•
Isolate power supply for laser marker from
other equipment.
•
Use noise cut transformer to absorb noises
from power supply.
Serial communication
control fails
Selected communication port is
inappropriate.
For communication with external devices, select
either RS-232C or Ethernet port. (They cannot be
used at the same time, or switched.)
The port selected in the environment setting
screen indicates the valid communication port.
RS-232C is selected at factory shipment.
Type of connection cable used is in
appropriate.
For RS-232C, use a commercially available cross
cable.
(A straight cable cannot be used.)
Laser marker has three-wire connection. (Only
pins Nos. 2, 3 and 5 of RS-232C connector are
used.)
For Ethernet, check the followings:
•
To use an external device and the laser marker
one to one, connect them with a commercially
available cross cable (STP cross cable of the
Category 5e or higher is recommended).
•
To use an external device and the laser
markers one to many, prepare a hub or
router compliant to 1000BASE-T, 100BASE-
TX, or 10BASE-T and connect them with a
commercially available straight cable (STP
cross cable of the Category 5e or higher is
recommended).
Communication parameter settings are
incorrect.
•
Match communication parameter settings to
external equipment. Communication parameter
settings of laser marker can be checked in the
environment setting screen.
•
When using RS-232C, specify the “Flow
control” to “None” at the communication port
settings of the external control device.
ME-LP400V-EX-6
Summary of Contents for LP-400 Series
Page 12: ...1 Before External Control ME LP400V EX 6...
Page 24: ...2 Control by I O ME LP400V EX 6...
Page 56: ...3 Control by Serial Communication RS 232 Ethernet ME LP400V EX 6...
Page 141: ...Troubleshooting ME LP400V EX 6...
Page 158: ...Character Code Table ME LP400V EX 6...
Page 176: ...Index ME LP400V EX 6...
Page 179: ...No 9000 0062 17V...
Page 180: ...Panasonic Industrial Devices SUNX Co Ltd 2003 2018 July 2018 9000 0062 17V...