Terminal
No.
Name/Description
B11
•
For NPN models *1
EMER.-: Output common for emergency stop
This terminal is connected to OUT COM. (B2) internally.
Connect this B11 with EMER.+ (B12) to release the emergency stop alarm.
The function relating to safety must be shut off mechanically. Therefore, it is recommended to wire these
terminals at no-voltage contact (dry contact).
•
For PNP models (“-C” in the end of the model name) *1
RESERVE: System reservation
Do not connect externally.
Notice
•
A11 and B11 on the I/O terminal block are available only for NPN type of laser marker. For PNP type, do not use these
terminals.
B12
EMER. +: Emergency stop input
Use this terminal to stop the laser radiation or disable the laser radiation by connecting with the safety
devices such as a door or a switch.
When between EMER.+ (B12) and OUT COM. (for NPN models; B11 or B2, for PNP models; A2) are
disconnected, the laser pumping is turned off and the laser radiation will be disabled.
The function relating to safety must be shut off mechanically. Therefore, it is recommended to wire these
terminals at no-voltage contact (dry contact).
*1 : Signals of A2, A11, B2 and B11 are different depending on the controller type of NPN or PNP.
•
NPN models: LP-4xx(T)U / LP-4xx(T)U-A / LP-4xxS9(T)U / LP-4xxS9(T)U-A / LP-VxxU / LP-VxxU-A / LP-W series
•
PNP models (with “-C” in the end of the model name): LP-4xx(T)U-C / LP-4xxS9(T)U-C / LP-VxxU-C
ME-LP400V-EX-6
Summary of Contents for LP-400 Series
Page 12: ...1 Before External Control ME LP400V EX 6...
Page 24: ...2 Control by I O ME LP400V EX 6...
Page 56: ...3 Control by Serial Communication RS 232 Ethernet ME LP400V EX 6...
Page 141: ...Troubleshooting ME LP400V EX 6...
Page 158: ...Character Code Table ME LP400V EX 6...
Page 176: ...Index ME LP400V EX 6...
Page 179: ...No 9000 0062 17V...
Page 180: ...Panasonic Industrial Devices SUNX Co Ltd 2003 2018 July 2018 9000 0062 17V...