![Omron SYSMAC 3G8F7-CLK12-E Operation Manual Download Page 99](http://html1.mh-extra.com/html/omron/sysmac-3g8f7-clk12-e/sysmac-3g8f7-clk12-e_operation-manual_1633420099.webp)
6-3
Section
Commands and Responses for the Support Board
83
6-3
Commands and Responses for the Support Board
6-3-1 Command Codes
Command
code
Data link operation
mode
Name
Page
code
Active
Inactive
04
01
Not valid
Valid
DATA LINK START
83
02
Valid
Not valid
DATA LINK STOP
84
05
01
Valid
Valid
CONTROLLER DATA READ
84
06
01
Valid
Valid
CONTROLLER STATUS READ
85
02
Valid
Valid
NETWORK STATUS READ
87
03
Valid
Valid
DATA LINK STATUS READ
89
04
Valid
Valid
CONNECTION CONFIGURATION INFORMATION
READ
90 (See note.)
05
Valid
Valid
NETWORK DISCONNECTION INFORMATION READ
91 (See note.)
06
Valid
Valid
NETWORK DISCONNECTION INFORMATION
CLEAR
93 (See note.)
08
01
Valid
Valid
ECHOBACK TEST
94
02
Valid
Valid
BROADCAST TEST RESULTS READ
94
03
Valid
Valid
BROADCAST TEST DATA SEND
95
21
02
Valid
Valid
ERROR LOG READ
95
03
Valid
Valid
ERROR LOG CLEAR
96
Note Command codes 06 04, 06 05, and 06 06 are supported only by the Optical Ring
Controller Link Support Boards in Token Ring Mode.
6-3-2 DATA LINK START
Starts the Controller Link Network data links.
Command Block
01
04
Command
code
Response Block
01
04
Response
code
Command
code
The DATA LINK START command can be received for manually set data links.
An error will occur if manually set data links are specified and yet data link tables
do not exist.
The node that receives this command and starts the data links will become the
data link startup node.
Note The Support Board can participate in automatically set data links, but it cannot
be the starting unit.