Section
9-3
Error Log
137
Error
code
Recorded
in
EEPROM
Correction
Detail code
Contents
Error
code
Recorded
in
EEPROM
Correction
2nd byte
1st byte
Contents
020C
Hex
Time out with token
00 Hex
Error status
(See note
3.)
Check network parameters, node
participation, cables, and
terminating resistance.
No
0210
Hex
Communications controller
transmitter error
00 Hex
Replace the Controller Link
Support Board.
Yes
0211
Hex
Duplicate node address error
(connected to SYSMAC LINK
by mistake)
00 Hex
Local node
address
Reset so that each node address
is used only once within the same
Network.
No
0214
Hex
Node address setting error
Not set
Correct the node address setting.
Yes
0216
Hex
Backup power supply error
00 Hex
Error type
01 Hex:
OFF to ON
02 Hex:
OFF to ON
Check the backup power supply
and the power supply cables.
Yes
021A
Hex
Set table logic error
00 Hex
01 Hex:
Network
parameters
02 Hex:
Data link
tables
03 Hex:
Routing
tables
Reset the appropriate data.
Yes
021B
Hex
Hardware error
00 Hex:
SL1 error
01 Hex:
SL2 error
Error status
(See note
3.)
Replace the Controller Link
Support Board.
No
021C
Hex
Data link error stopped
Not set
Stop the user application, reset
the computer, and retry.
Yes
021E
hex
Network line disconnection
Ring status (See node 4.)
Refer to information in previous
sections of this manual.
Yes
0220
hex
Additional information 1 for
number of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 1 to
16
Check the network parameters,
the disconnected node, and the
cables.
No
0221
hex
Additional information 2 for
number of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 17 to
32
No
0222
hex
Additional information 3 for
number of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 33 to
48
No
0223
hex
Additional information 4 for
number of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 49 to
62
No
0300
Hex
Packet discarded
Not set
Conduct an echoback test and
find the cause of the error.
Yes
0601
Hex
Unit error
Not set
Check the operating environment.
Yes
Note
1. Errors indicated by error codes 0101 to 0116 are recorded only when the
frame was discarded because transmission was impossible.
2. Error codes 021E to 0223 Hex are recorded only for Optical Ring Networks.