7-3
Section
Setting Routing Tables
108
Note
1. The unit number is set between 00 and 15 using the rotary switch on the front
panel of CV-series and CS1-series Controller Link Units, and is the same as
the operating level for C200HX/HG/HE PCs. For the Support Board, the unit
number is 16 less that the unit address (i.e., the Communications Unit num-
ber) set for the Board in the FinsGateway settings.
2. The network address is the address of the network connected to the Unit
(between 1 and 127). The address is set when the local network table is
created.
A relay network table provides the node and network addresses corresponding
to the initial relay point (first point the data must go to) en route to a target net-
work (end network) not directly connected to the local PC. The table traces the
route from the relay point to the end network.
Local net-
work ad-
dress
Unit
number
End
network
Relay
node
Computer relay network table
Relay
network
Network address 1
Local node
Computer
Node
address
1
Node ad-
dress 3
Node ad-
dress 1
Relay node
PC (a)
Relay node
PC (b)
Node address 2
Unit number 0
Node ad-
dress 1
Unit num-
ber 1
Node address 2
Destination
Network
address 2
Network
address 3
End
network
2
3
Relay
network
1
1
Relay
node
3
3
3
PC (a) relay network table
2
2
2
PC (b) local network table
0
End network
3
1
Data first goes to node
address 3 at network
address 1 to reach
network address 3.
Data then goes to node
address 2 at network ad-
dress 2 to reach network
address 3.
We know from the
local network table
that the data goes
through local unit
number 1 to reach
network address 3.
Data goes to node
address 2 at net-
work address 3,
i.e., the local net-
work.
Node address 2
7-3
Setting Routing Tables
This section describes routing table settings.
Routing tables are set through the FinsGateway, Controller Link Support Soft-
ware, or CX-Programmer. This section describes setting procedures and setting
details.
For specific procedures, see the FinsGateway online help, Controller Link Sup-
port Software Operation Manual (W308,) or CX-Programmer User’s Manual.
Relay Network Table