2-1
Section
Connecting Wired Systems
26
Note
1. If the connector is disconnected, communications for the Board that was
disconnected with other nodes in the network will be disabled and the net-
work will be split into two at point of disconnection. Utmost care is necessary
to prevent disconnection of a connector during communications.
Controller Link Support Board
Communications disabled
Connector
Network split
(communications disabled).
2. Do not pull on a communication cable.
3. When bending a communications cable, allow 60 mm or more for the bend-
ing radius (R).
4. Do not place heavy objects on the communications cable.
5. Supply power only after checking the wiring thoroughly.