Make sure that the LNK
indicator is ON at nodes
participating in the active
data links.
5-4
Section
Checking Data Link Status
75
5-4
Checking Data Link Status
There are two methods for checking the status of active data links:
•
Check the LED indicators on the front of the Units.
•
Check the data link status area.
5-4-1 LED Indicators
Check the LNK indicator on the front of the Board.
Optical Ring Unit
(H-PCF or GI Cable)
Wired Unit
Name
Color
Status
Contents
LNK
(d
li k)
Yellow
ON
Participating data links.
(data link)
Flashing
Data link table setting error.
OFF
Not in data links or data links are inactive.
The LNK indicator will be lit at all node participating in the data links as long as
operation is normal. The data link mode (manual/automatic) can be checked us-
ing the M/A indicator. The M/A indicator is only available in the Controller Link
Unit and cannot be used in the Controller Link Support Board. See 9-1 Trouble-
shooting Using Indicators for details.
5-4-2 Data Link Status Area
The data link status area can be used to check for errors when data link does not
operate normally even though no abnormality has been detected by the comput-
er or the Controller Link Support Board.
Data link status can be monitored using the CLK Data Link Setting Utility in Fins-
Gateway or it can be stored in FinsGateway event memory. Refer to the Fins-
Gateway online help and installation guide for details.